Eltek Flatpack S -48V, 2 Rectifiers Shelf 4 MCB Circuit Breakers, 2 CBB Circuit Breakers
US$2,299.99
Product Information
- Description
- Specifications
Eltek CTOS0201.002
Flatpack S -48V, 2 Rectifiers Shelf 4 MCB Circuit Breakers, 2 CBB Circuit Breakers
Flatpack S Power System Front/Rear Wire 40Amp Max, Lvbd 48V Negative Output Polarity 19" / 1Ru / Flush Or Mid Mount Individual Ac Inputs To System (Lu Ac Cord) 2Qty Rectifier Positions, E/W 2X 1000W 48V Rectifiers (241122.105) Front Access Pluggable 4Qty B Frame Distribution Load Circuit Breaker Positions Up To 20Amps Max (10Awg Max), E/W 2X 20A & 2X 15A Breakers 2Qty Lvbd Installed 60Amp Battery Bullet Cirucit Breaker Positions (6Awg Max) 242100.410 Smartpack S Controller Included.
Specifications CTOS0201.002
INPUT DATA | |
Voltage | 100 - 250VAC |
Mains Configuration | 230VAC, 1 phase or 2 x 1phase |
Mains Connection | 2,5mm2 Terminal blocks, rear connection |
Frequency | 45 to 66Hz |
OUTPUT DATA | |
Voltage | 48Vdc |
Max. Current | 40A |
LVBD | Default |
Breaker (Plug-in type) maximum size | 2 x 40A1) |
Connection (rear) | 16mm2 Terminal blocks |
LOAD DISTRIBUTION | |
Rear connections | N/A |
Rear cabel entry, front access | 7 x 20A MCB 2) |
Connections, screw terminals Optional LVLD | 7 X 4mm2 on MCB 1 and 2 |
Front connections | 4 x 20A MCB / 7 x 15A Fuse |
Plug-able screw terminals | 4mm2 |
CONTROL & MONITORING | |
Smartpack S | 6x Input/Output and Ethernet, See Smartpack S datasheet |
MECHANICAL DATA | |
Dimensions (W/H/D) | 19"/1U/262mm Recommended minimum cabinet depth, 300 mm |
Weight | 5.3 kg [11.7 lbs] |