• Home
  • ALGcom DC UPS 48V 25A Manageable SNMP

ALGcom DC UPS 48V 25A Manageable SNMP

(0)No Reviews yet
US$‎1,300.00
  • SKU: FN-4800-25-SNMP
  • Manufacturer: ALGcom
  • Data Sheet: Download
  • Installation Guide:Download
 Open chat or call us for stock status

Product Information

ALGcom FN-4800-25-SNMP

DC UPS 48V 25A Manageable SNMP

The FR and FN DC UPS families receive AC power from the utility grid and provide stabilized DC power at their output. In the absence of AC power, the battery bank supplies power to the loads. The battery bank operates continuously and in a floating mode, supplying DC power without interruptions.

The Rectifier ensures uninterrupted power supply even under adverse conditions. Through its PFC controller circuit, it operates with high energy conversion efficiency, guaranteeing stable and high-quality power at its output. The product is equipped with protective circuits at its input and outputs, making it suitable for application in harsh environments with high operational criticality or where the utility's power supply quality is unstable.

The models in the SNMP version features advanced remote management and monitoring capabilities via SNMP-V2 protocol, combined with its ease of use and flexibility in configuring the battery bank. The output circuit is monitored and managed by a microprocessor, which continuously assesses the battery charge status. During a recharge situation, the recharging circuit operates intelligently, aiming to charge the batteries according to their best current condition. This procedure ensures the extended durability of the entire battery bank and is performed through 03 stages of recharge.


Applications:

  • Critical Power Loads;
  • Telecommunication Networks;
  • Alarm Systems.

Features:

  • ST/SNMP/SNMP-X
  • Floating Output Voltage;
  • Dual-stage Energy Conversion;
  • Active Power Factor Correction (PFC);
  • Intelligent charging system operating through 3 stages of battery recharge;
  • Smart Fan technology;
  • Includes 19" mounting brackets and a sensor cable for PoP temperature measurement.
  • SNMP/SNMP-X
  • Ethernet for remote or local monitoring via SNMP-V2 and control through a Web page;
  • Compatible with Zabbix, Grafana, LibreNMS and The Dude monitoring systems;
  • System for measuring input AC voltage, output voltage and current, battery voltage and current, and external and internal temperature;
  • Monitoring of alerts through Web page (Overtemperature, Overload, Battery charging and discharging, and Ventilation failure);
  • Allows battery voltage compensation based on temperature variation;
  • Remote testing of battery bank autonomy;
  • Compatible with Lithium batteries;
  • Suitable for hybrid connection with solar power.

Specifications

Specifications FN-4800-25-SNMP

Weight2.5 lbs
Dimensions (L x W x H)1.80” x 17.5” x 10”
Nominal Input Voltage100 – 240 VAC
Input Voltage Range100 – 270 VAC
Frequency50/60 Hz
Input Current14.67 ARMS / 6.11 ARMS (100/240 VAC)
ProtectionsTwo 15 A circuit breakers for short- circuit and overload protection, one for the Line and another for the Neutral
ProtectionsVaristor: 300 VAC, 170 J varistor for protection against lightning and electrical surges
Undervoltage: Disconnects the AC-DC converter if voltage <100 VAC
Overvoltage: Disconnects the AC-DC converter if voltage >270 VAC
Output CharacteristicsFN-4800-25 ST/SNMP/SNMP-X
Nominal Output Voltage54 VDC
Output Voltage Range42 - 58 VDC
Maximum Output Current25 A
Maximum Output Power1450 W
Adjustable Battery Charging Current1/5/10/15 A Via Selector Switch; 1 - 15 A Via Web Page (SNMP)
Battery Fuse for short- circuit and overload protection25 A
Short CircuitShort-circuit current <5 A with automatic rearming
OvercurrentLimits the output current to the nominal value of 26.5 A
DeratingLimits the output current to 15 A in case of ventilation failure
Limits the output current to 15 A if the internal temperature of the heat exchangers is above 75°C "
Limits the output current to 20 A if the input voltage is below 110 VAC
OvervoltageDisconnects the AC-DC converter if the output voltage is >60 VDC
Battery UndervoltageDisconnects the battery bank if the voltage is lower than the configured voltage (Default voltage 42 VDC)
OvertemperatureDisconnects the AC-DC converter if the temperature > 80°C and reconnects at 70°C
General SpecificationsFN-4800-25 ST/SNMP/SNMP-X
Power Factor (Rated Load)0.98 / 0.98 (127/ 220 VAC)
Efficiency>92 % (full load)
Line+Neutral Isolation for Output3000 VAC
Line+Neutral Isolation for Ground2500 VAC
Output Isolation for Ground1000 VAC
Operating Temperature-10 ºC até 60 ºC
Operating Humidity20 a 90 % (non-condensing)
Alarm Red LEDOvertemperature, Overload, Ventilation Failure (Blinking)
Alarm Green LEDBattery Charging, Battery Discharging, and AC Power
Alarms Web Page (SNMP)Minimum AC Input Voltage, Maximum AC Input Voltage, Overload, Overtemperature, Output Overvoltage, Ventilation Failure, Temperature Sensor Failure, Battery Charging, and Battery Discharging
Digital Inputs (SNMP-X)0 - 60 VDC (voltage greater than 5 VDC, logic level 1)
Digital Relay Output (SNMP-X)60 VDC 1 A
Installation Mode1 U height for 19" racks

Reviews

Ratings & Reviews

No reviews available

Be the first to Write a Review